电流传感器 / CS11-L
Limited Availability ›
This product has limited availability. Some accessories, replacement parts, or services may still be available when it is no longer available.
CS11-L AC Current Sensor
Measure the ac Current along an Electrical Wire
气象 应用支持 水资源 应用支持 能源 应用支持 湍流通量 应用支持 基础结构/工业设施 应用支持 土壤 应用支持

概览

The CS11 monitors ac current along an electrical wire. It outputs a millivolt signal that many of our dataloggers can directly measure.

优势与特点

  • Ideal applications include motor or generator load conditions, efficiency studies, intermittent fault detection, and rough submetering
  • Sensor is external to the wire jacket and has no direct electrical connection to the system

图像

Top view
Top view
Top view
Bottom view

技术说明

The CS11 uses CR Magnetic's CR8459 Current Transformer to detect the ac current along an electrical wire using the magnetic field that is generated by that current. The CS11 is external to the wire jacket and has no direct electrical connection to the system.

The CS11 is recommended for measurements that do not require high accuracy, such as motor or generator load condition monitoring, efficiency studies, intermittent fault detection, and rough submetering.

产品规格

Measurement Range 0.15 to 200 A (0.15 to 125 A for CR200X)
Frequency 50 and 60 Hz
Insulation Resistance 100 MΩ (@ 500 Vdc)
High Potential 2000 V
Rated Current 200 A, 125 A (CR200X)
Accuracy Typically ±1% of actual value with provided multiplier (with 10 Ω maximum burden [resistive])
Multiplier iMult=200 A/1000 mV=0.2
操作温度范围 -25° to +55°C
Storage Temperature Range -25° to +70°C
Case Material Polypropylene resin
Construction Epoxy encapsulated
Inner Diameter 1.9 cm (0.75 in.)
Outer Diameter 4.8 cm (1.89 in.)
Height 1.7 cm (0.67 in.)

兼容性

Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.

数据采集器

Product Compatible Note
CR1000X
CR300
CR3000 (retired)
CR310
CR350
CR6
CR800 (retired)
CR850 (retired)

相关技术文档


常见问题解答

CS11-L: 5

展开全部收起全部

  1. Connect the red wire to ground rather than its normal location on the CR200(X).

  2. Not directly. If the CS11-L is connected to a data logger, the data logger can take the ac measurement and control a solid-state relay based on some threshold within the data logger program. The solid-state relay can then control other relays, solenoids, or motor starters. (Use of a solid-state relay is preferred because the data logger can trigger it with a small 5 Vdc mA signal.)

  3. Yes. Three CS11-L sensors can be connected to a data logger to measure the amperage on each of three phases.

  4. The following are some of the features of the CS11-L:

    • The quality of the measurements was improved by upgrading the 10 ohm internal resistor.
    • The CS11-L is compatible with the CR200(X)-series dataloggers, as well as all of the data loggers that were compatible with the CS10-L. This allows the CS11-L to replace both the CS10-L and the CS15-L.
    • The programming examples were improved to give greater stability to the measurements. On some data logger models, the ACPower() instruction can be used.
  5. No. The CS11-L is an ac-only sensor.

案例研究

埃及: 图坦卡蒙墓保护
In 1922, when the intact tomb of Tutankhamen was discovered in Egypt's Valley of the......阅读更多