CURS100让Campbell Scientific数据采集器可以测量输出电流信号(例如:4-20 mA)的传感器或输出设备。它将电流信号转换成电压信号。
CURS100采用一个100欧姆的精密并联电阻,可以让最大25 mA的电流信号被 ±2500 mV 量程(CR10X,CR510)所读取,以及让最大50 mA的电流信号被 ±5000 mV 量程所读取。
Used With | Sensors that output a current signal (4 to 20 mA) |
Resistance | 100 Ω (shunt—bulk metal foil) |
Tolerance | ±0.01% (@ 25°C) |
Power Rating | 0.25 W |
Maximum Temperature Coefficient | ±0.8 ppm/°C |
Dimensions | 1.5 x 1.5 x 2.7 cm (0.6 x 0.6 x 1.0 in.) for body with prongs |
Weight | 6 g (0.2 oz) |
Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.
Product | Compatible | Note |
---|---|---|
21X (retired) | ||
CR10 (retired) | ||
CR10X (retired) | ||
CR200X (retired) | ||
CR206X (retired) | ||
CR211X (retired) | ||
CR216X (retired) | ||
CR23X (retired) | ||
CR295X (retired) | ||
CR300 (retired) | ||
CR3000 (retired) | ||
CR310 | ||
CR350 | ||
CR500 (retired) | ||
CR5000 (retired) | ||
CR510 (retired) | ||
CR6 | ||
CR800 (retired) | ||
CR850 (retired) | ||
CR9000 (retired) | Compatible CR9000 modules are the CR9050 and the CR9052; the CR9051 is partially compatible. |
Our multiplexers are compatible with the CURS100.
Current CR10X Wiring Panels can accommodate both the CURS100 and the cover associated with the CR10XTCR (reference thermistor for thermocouple measurements). Specifically, the physical configuration of the thermocouple cover, the data logger input terminals, and the terminal input modules allow sufficient room for the cover to be used with the CURS100 attached. In contrast, older CR10TCR covers are not deep enough.
Note: The CR6 (serial number >7501), CR1000X, CR350, CR300, and CR310 data loggers can do current measurements without the CURS100.
The CURS100 output is measured with VoltDiff Instruction in CRBasic and with Instruction 2 (Differential Voltage) in Edlog. The CURS100 consumes one differential analog input; an adjacent analog ground channel accepts the analog "ground prong" of the CURS100. Not all data logger terminal strips have this sequence on all channels, so please check your data logger's wiring panel to confirm channel assignments, especially if you plan to use multiple terminal input modules.
CURS100: 1